IMPERIAL's FIRE BARRIER LATEX PRIMER/PAINT
Test Results - Drywall Tests
|
Test: ASTM 119 on Standard Wall Assembly U-338
|
Equivalent tests: N/A
Testing Agent: Southwest Research Institute
Date: November 4, 2004
Substrate: Std. Stud wall with Sheetrock
Method: ASTM 119 time temp curve screening test
Observations: 1 Hour 25 min 15 sec
Test Results - Drywall Tests
|
|
Test: NFPA 286, Standard Methods of Fire Tests for Evaluating
Contribution of Wall and Ceiling Interior Finish to Room Fire Growth
|
Equivalent tests: N/A
Testing Agent: Omega Point Laboratories
Date: 8/12/02
Substrate: Dry Wall
Method: The potential for the spread of fire to objects
outside the room of origin is evaluated by the measurement of the total heat
release of the fire.
Observations: The sample did not spread flames to the
ceiling during the 40kW exposure, nor did the flames spread to the extremities
of the 12 foot walls during the 160kW exposure. The sample did not exhibit
flashover conditions at any time during the test.
|
|